Water (Cartridge Operated) Fire Extinguisher – 9 LTR with Mild Steel body and distilled water charge. Effective on Class A (solid fuel) fires.

  • Capacity: 9 LTR
  • Type: Gas Cartridge Operated
  • Gas Cartridge: 60 g CO₂ (IS 4947)
  • Fire Rating: 2A (Class A – Solid Fuel)
  • Fire Classes: Class A
  • Effective Discharge Time: Minimum: 13 sec. (Actual: Approx. 40 sec.)
  • Bulk Range of Discharge: Minimum: 2 m (Actual: Approx. 4.5 m)
  • Percentage of Discharge: Minimum: 95% (Actual: Approx. 97%)

Speak to our fire safety expert to learn more about this product.

Product Description

Water (Cartridge Operated) 9 Litre Fire Extinguisher suitable for Class A fires.

Lightweight, durable, and compliant with safety standards. Water Fire Extinguisher with a nominal charge of 9 litres (±5% by volume), fitted with a 60 g CO₂ Gas Cartridge conforming to IS 4947. Constructed from Mild Steel (MS) Sheet using the MIG welding process with a forged brass discharge valve.

1. General Data

ParameterSpecification
ManufacturerPalladium Safety Solutions Pvt. Ltd.
Trade Mark / BrandPALEX
BIS Standard CodeIS 15683:2018
TypePortable Fire Extinguisher (Gas Cartridge Type)

2. Performance Data

ParameterSpecification
Capacity9 LTR
Fire Rating2A (Class A – Solid Fuel)
Effective Discharge TimeMinimum: 13 sec. (Actual: Approx. 40 sec.)
Bulk Range of DischargeMinimum: 2 m (Actual: Approx. 4.5 m)
Percentage of DischargeMinimum: 95% (Actual: Approx. 97%)
Working Temperature+5°C to +60°C
Service Pressure15 BAR
Maximum Service Pressure17 BAR

3. Material of Construction

ComponentMaterial
BodyMild Steel (MS) Low Carbon Welded Sheet (Max. 0.25% Carbon, 0.05% Phosphorus, 0.05% Sulphur) conforming to IS 513
Extinguishing MediaDistilled Water (9 Litres)
Neck RingMS Pipe (Filling Dia – 64 mm)
ValveBrass, Squeeze Grip Type
Syphon TubePVC / Plastic
StrainerPlastic
Gas Cartridge60 g CO₂ Gas Cartridge as per IS 4947
Hose PipePVC Braided (550 mm ± 10 mm)
Discharge NozzlePVC
Bottom DomePVC / Plastic

4. Quality Test

TestSpecification
Hydro Pressure Test (Pt)35 bar (3.5 MPa), Hold for 1 minute
Minimum Burst Pressure (Pb)55 bar (5.5 MPa), Hold for 1 minute
Leakage TestInverted Glass Jar / Soap Solution
Partial DischargeThe second pressure or weight shall not be less than 75% of the first after interruption of discharge

5. Dimensions

ParameterSpecification
Diameter171 mm ± 2 mm
Height550 mm ± 2 mm
Height with Bottom Dome570 mm ± 2 mm
Thickness1.5 mm Thick Sheet
Full / Gross Weight12.5 KG ± 2% (Approx.)

6. Anti-Corrosion Treatment

The extinguisher undergoes a 7-tank anti-corrosion process, followed by an epoxy powder coating with a minimum thickness of 50 microns.

7. Miscellaneous

ParameterSpecification
Inspection & TestingAs per approved QAP
FinishPO Red as per IS:5 (Shade 538)
MarkingAs per IS 15683:2018
ApprovalsBIS (Bureau of Indian Standards)
Maintenance, Care & RefillingAs per IS 2190

8. Packing

ParameterSpecification
Box TypeCorrugated Boxes
Box Dimensions190 mm × 190 mm × 600 mm

9. In-Box Accessories

ItemQuantity
Wall Mounting Bracket1 No.
Fire Extinguisher1 No. (Fully Assembled)