The Palex 16-Zone Fire Alarm Panel is a microcontroller-based control panel designed to serve as the central hub of conventional fire alarm systems. It supports a wide range of fire detection and safety devices, including gas leak detectors, manual call points, sprinkler supervision systems, and other fire safety equipment.
Its intuitive user interface, advanced monitoring capabilities, and reliable performance make it suitable for commercial, industrial, institutional, and residential installations.
Speak to our fire safety expert to learn more about this product.
| Parameter | Details |
|---|---|
| Manufacturer | Palladium Safety Solutions Pvt. Ltd. |
| Trade Mark / Brand | PALEX |
| Type | Conventional Fire Alarm Panel |
| Product Code | PSS-16Z |
| Specification | Details |
|---|---|
| Operating Voltage | AC 220V ±10%, 50Hz |
| Internal Power Supply | Regulated DC 24V / 5A |
| Hooter Output | 4A (24V DC) |
| End of Line Resistor | 4.7k Ohm Per Zone |
| Power Consumption | Optimized for Low Standby Current |
| Battery Charging | Trickle & Fast Charging Supported |
The panel operates on a standard AC 220V power supply and delivers a regulated 24V DC output for connected fire alarm devices.
A dedicated 4A hooter output supports audible alarm devices for effective emergency notification.
Built-in trickle and fast charging functionality ensures reliable backup battery performance during power failures.
The panel is designed to minimize standby power usage while maintaining continuous system monitoring.
| Specification | Details |
|---|---|
| Operating Temperature | 0°C to +50°C (32–F to 122–F) |
| Storage Temperature | -10°C to +60°C (14–F to 140–F) |
| Operating Humidity | Up to 95% RH (Non-Condensing) |
| Installation Environment | Indoor, Dust-Free, Ventilated |
The panel is designed to operate consistently in varying environmental conditions while maintaining dependable fire detection performance.
Suitable for installation in clean, dry, and properly ventilated indoor environments.
| Specification | Details |
|---|---|
| Dimensions (H × W × D) | 350 mm × 420 mm × 130 mm |
| Weight | 7 kg |
| Construction Material | 1.8mm CRCA Sheet, Powder Coated |
| Colour | Caramel White |
| Mounting Type | Wall Mounted |
Manufactured using heavy-duty 1.8mm CRCA sheet with powder-coated finishing for enhanced durability and corrosion resistance.
The panel is designed for convenient wall-mounted installation in fire control rooms and monitoring areas.
| Specification | Details |
|---|---|
| Number of Zones | 16 |
| Zone Wiring Type | 2-Wire |
| Indication | Fire, Open, Short (LED Indication) |
| Isolation Facility | Zone-Wise Switch Isolation |
| Testing | Zone-Wise Fire, Open, Short Test |
The panel supports 16 separate monitoring zones for efficient fire detection management.
Each zone features dedicated LED indicators for fire, open-circuit, and short-circuit conditions.
Individual zones can be isolated for maintenance, troubleshooting, or testing purposes.
Zone-wise testing enables quick verification of fire, open-circuit, and short-circuit conditions.
| Specification | Details |
|---|---|
| Display Type | 16×2 Character Alphanumeric LCD |
| LED Indications | Mains ON, Battery Low, AC Fail, Charging, Reverse, Fire, Fault |
| Control Buttons | Reset, Alarm Cancel, Lamp Test, Zone Test, Zone Isolate |
A 16×2 alphanumeric LCD provides real-time system notifications and operational information.
Dedicated LEDs display power status, charging status, fire conditions, faults, and battery conditions.
Simple control buttons allow operators to reset alarms, perform lamp tests, isolate zones, and conduct system testing.
| Specification | Details |
|---|---|
| Detector Compatibility | Supports Any Conventional Detector |
| External Interface | Potential-Free Fire & Fault Contacts |
Compatible with conventional smoke detectors, heat detectors, manual call points, and related fire alarm devices.
Provides fire and fault relay outputs for integration with external monitoring systems and building automation systems.
12 Months from the Date of Invoice
| Specification | Details |
|---|---|
| Product Code | PSS-16Z |
| Zones | 16 |
| Operating Voltage | AC 220V ±10%, 50Hz |
| DC Supply | 24V / 5A regulated |
| Hooter Output | 4A @ 24V DC |
| EOL Resistor | 4.7k × per zone |
| Wiring | 2-wire per zone |
| Display | 16×2 LCD |
| Dimensions | 350×420×130 mm |
| Weight | 7 kg |
| Colour | Caramel White |
| Warranty | 12 Months from invoice |
Drag to pan · Scroll or pinch to zoom · +/- buttons · Arrow keys to move
Could not display this PDF in the browser.
A 16 Zone Fire Alarm Panel is a conventional fire alarm control panel that monitors and manages fire detection devices across 16 independent zones.
The panel serves as the central monitoring and control unit of a fire detection system.
The panel supports conventional smoke detectors, heat detectors, gas leak detectors, and manual call points.
Yes, it supports backup batteries with trickle and fast charging functionality.
The panel indicates Mains ON, Battery Low, AC Fail, Charging, Reverse, Fire, and Fault conditions.
Yes, each zone can be individually isolated using dedicated switches.
Yes, fire, open circuit, and short circuit testing are available for each zone.
Yes, it supports all standard conventional detectors.
Yes, it supports Building Management System integration through potential-free contacts.
The panel is designed for wall-mounted installation.
Yes, it is suitable for industrial, commercial, residential, and institutional applications.
A 16 Zone Fire Alarm Panel provides reliable fire detection, flexible zone management, easy maintenance, and comprehensive protection for medium-sized facilities.
Browse our range, explore partnership opportunities, or request a call-back from our team.
Fill in your details — we’ll call you back shortly. Fields marked * are required.