In the event of Fire, Fault, or Short Circuit conditions, the panel identifies the affected zone and performs the required actions such as activating common or zone-wise hooters. This latest technology fire alarm panel is specifically designed for commercial buildings and medium-scale industries where reliable fire monitoring and alarm management are essential.

Speak to our fire safety expert to learn more about this product.

Product Description

1. General Data

ParameterDetails
ManufacturerPalladium Safety Solutions Pvt. Ltd.
Trade Mark / BrandPALEX
TypeConventional
Product CodePSS-10Z

2. Features and Benefits

Advanced Microcontroller Based Fire Alarm Panel

Provides intelligent monitoring and reliable fire detection management. The microcontroller architecture enables fast event processing, accurate fault identification, and dependable performance in fire emergencies.

16×2 Character LCD Display

Displays system status, alarms, and fault information in real time. The LCD interface improves system visibility and helps operators respond quickly to fire incidents and maintenance requirements.

Comprehensive Status Indications

  • Mains ON
  • AC Fail
  • Open
  • Fuse
  • Charging
  • Reverse Polarity (Rev)
  • Battery Status

Multiple LED indicators provide complete system monitoring, ensuring operators can instantly identify power, battery, and fault conditions.

Zone Wise Fire, Open & Short LED Indications

Dedicated LED indications for each zone. Zone-specific status indicators help maintenance personnel quickly identify the exact location of fire alarms and wiring faults.

Zone Wise Hooter Option

Supports both zone-wise and common hooter operation. Flexible hooter control allows targeted alarm notification and improved emergency response management.

Zone Isolation Facility

Allows isolation of individual zones through switches. Zone isolation simplifies maintenance and testing while keeping the remaining fire detection system operational.

Extra Potential Free Contacts

Provides fire and fault relay outputs. Potential-free contacts allow integration with Building Management Systems (BMS), automation systems, and third-party monitoring equipment.

Control Functions

  • Reset
  • Alarm Cancel
  • Lamp Test
  • System Controls

Easy-to-use control functions improve system management and operational efficiency.

Trickle & Fast Charging Facility

Built-in battery charging support. The charging system ensures backup batteries remain fully charged and ready during power failures.

Universal Detector Compatibility

Compatible with any conventional detector. The panel works seamlessly with conventional smoke detectors, heat detectors, manual call points, and other fire detection devices.

Common Fire & Fault Annunciation

Provides centralized notification for alarms and faults. The annunciation system ensures building operators receive immediate alerts during emergency events.

3. Technical Specifications

SpecificationDetails
Mains Voltage220V AC
Frequency50 Hz
Power Consumption120 Watt (Fire Condition)
Operating Voltage24 V DC
Detection Output24 V DC
Hooter Output Supply24 V DC
Number of Relays14

The Fire Alarm Panel – 10 Zone operates on a standard 220V AC power supply and provides regulated 24V DC outputs for detectors and alarm devices. With 14 relay outputs, it offers versatile control and integration capabilities for fire alarm systems and building safety infrastructure.

4. Initiating Device Circuits (Zone Circuit)

SpecificationDetails
Normal Operating Voltage16–24 V DC
Maximum Zone Resistance220 Ohms
End of Line (EOL)4k7 Ohm, 1 Per Zone
Standby Current200 mA

The zone circuits are designed to provide stable monitoring and fault detection across all fire alarm zones. End-of-line monitoring ensures system integrity while minimizing false alarms and wiring issues.

5. Environmental Information

SpecificationDetails
Operating Temperature0°C to 55°C
Operating Humidity5% to 95% RH (Non-Condensing)

The panel is designed to operate reliably across a wide range of environmental conditions, making it suitable for commercial, industrial, and institutional facilities.

6. Mechanical Specifications

SpecificationDetails
Cabinet TypeCRCA with Powder Coated Finish
ColourCaramel White
Dimensions345 mm × 420 mm × 122 mm
ApprovalsCE
Maintenance StandardAs per IS 15908:2021

Manufactured using a durable powder-coated CRCA enclosure, the Fire Alarm Panel – 10 Zone provides long-lasting protection and compliance with recognized fire alarm maintenance standards.

7. In-Box Accessories

ItemQuantity
Fire Alarm Panel1 Nos
explore-business icon

Have questions?

We will be happy to help you. Please, fill this small form and help our customer support manager to contact you with all the details.

Take action

Browse our range, explore partnership opportunities, or request a call-back from our team.

grid image